- Eight-channel dimmer module for commercial lighting applications
- Installs in a Crestron® CAEN or CAEN-MLO enclosure
- Supports dimmable incandescent, magnetic low-voltage, neon/cold cathode, and 2-wire fluorescent lighting loads
- Single or dual feeds - two four-channel dimmers in one module
- Rated 16A per channel, 32A total (using two 20A feeds), at 120VAC
Provides eight channels of dimming for commercial lighting applications. Supports incandescent, magnetic low-voltage, neon/cold cathode, and 2-wire dimmable fluorescent lighting loads. Installs in a CAEN or CAEN-MLO wall mount automation enclosure as part of a complete Crestron® centralized lighting control system.
The Crestron® GL-CAEN-2DIM8 is an eight-channel, two-feed dimmer module designed for 120V commercial lighting system applications. It installs in a CAEN or CAEN-MLO enclosure and provides control of a variety of dimmable lighting load types including incandescent, magnetic low-voltage, neon/cold cathode, and 2-wire fluorescent. Dual feed capability provides two independent four-channel dimmers in one module space. Each output channel is rated for 1920 Watts (16 Amps), with a total module rating of 3840 Watts (32 Amps) when fed from two separate 20 Amp feeds.
Forward Phase Dimming
The GL-CAEN-2DIM8 employs forward phase (leading edge) dimming to handle inductive load types like magnetic low-voltage and neon, as well as incandescent and 2-wire fluorescent.
Air-Gap Relays
An air-gap relay on each channel output allows individual circuits to be serviced without disabling the entire module.Â
Silent Operation
Low-maintenance convection cooling with over-sized heatsinks affords silent operation with no mechanical components to wear out.
Emergency Lighting Control
The GL-CAEN-2DIM8 is UL® 924 and CSA® C22.2 No. 141-15 listed for use in controlling emergency lighting loads. In the event of a power failure, a contact closure from a power loss sensor (Crestron GLS-PLS-120/277, sold separately) activates the override mode in the GL-CAEN-2DIM8 to turn on each designated lighting load if it is off (assuming line power is supplied by a backup power source). The override dimming level can be preset to any value when commissioning the lighting system, so even if the load is already on prior to a power failure, it will change to the preset level when override mode is activated.
Â
- Eight-channel dimmer module for commercial lighting applications
- Installs in a Crestron® CAEN or CAEN-MLO enclosure
- Supports dimmable incandescent, magnetic low-voltage, neon/cold cathode, and 2-wire fluorescent lighting loads
- Single or dual feeds - two four-channel dimmers in one module
- Rated 16A per channel, 32A total (using two 20A feeds), at 120VAC
- Forward phase dimming
- Customizable dimming curves via software
- Built-in air gap relay per channel
- Convection cooled for silent operation
- Closure-activated override mode
- UL® 924 and CSA® C22.2 No. 141-15 listed for emergency lighting control
- Crestron system integration via Cresnet®
- Includes terminal block for high-voltage wiring
- CEC Title 24 2013 compliant
- Spec Sheet available - Yes
- Depth: 3.43 in
- Height: 7.59 in
- Width: 6.92 in
- AC Voltage: 120 Volts
- Product Weight: 4.50 lbs
- Certifications: CE, UL, FCC
- Operating Temperature (Maximum): 104 F
- Operating Temperature (Minimum): 32 F
- Load Control:
•Dimmer Channels: 8
•Dimmable Load Types: Incandescent, magnetic low voltage, neon/cold cathode, 2-wire fluorescent
•Per Channel Load Rating: 16A (1920W)
•Per Group Load Rating: Group 1 (Channels 1-4): 16A (1920W), Group 2 (Channels 5-8): 16A (1920W)
•Module Total Load Rating: 32A (3840W)
•Minimum Load: 25W
•Line/Load Voltage: 120VAC, 50/60Hz, requires one or two single-phase feeds (may be same phase or split phase) - Connections :
•Via Terminal Block (included):
•Line 1 - 2: (2) Screw terminals, black, line power feed inputs (per group)
•DIM 1 - 8: (8) Screw terminals, red, load outputs (per channel)
•N In 1 - 2: (2) Screw terminals, white, line power feed neutrals (per group)
•N Out 1 - 8: (8) Screw terminals, white, load neutrals (per channel)
•Note: Each terminal accepts one 14-10AWG wire
•Module Interconnect: (2) 5-pin 0.156-inch headers
•Cresnet/Override interconnect ports
•Each connects to the adjacent module using the interconnect jumper provided
•Connects to a CAEN-BLOCK (sold separately) when installed in the lowest position within the enclosure - Controls and Indicators:
•PWR: (1) Green LED, indicates line power is applied to the LINE 1 terminal
•NET: (1) Yellow LED, indicates Cresnet communication with the control system
•SETUP: (1) Pushbutton and (1) red LED, used to enter Local mode and test each channel
•1 - 8: (8) Red LEDs, each indicates the status of the corresponding channel - Environmental:
•Humidity: 10% to 90% RH (non-condensing)
•Heat Dissipation: 26 BTU/hr + (4.7 BTU/hr x load current in Amps), 176 BTU/hr at maximum load - Enclosure:
•Gray metal with black heat sink, surface mount module with (2) integral mounting flanges